Hi all, can the PH massive help me with this plug on my 2.3kva generator.
I cannot seem to find a plug to fit, the only 240v ones I can find are the three pin type.
It has an earth point to the right, you can just see it in the pic, but only two pin holes?

That becuase its a french type socketI cannot seem to find a plug to fit, the only 240v ones I can find are the three pin type.
It has an earth point to the right, you can just see it in the pic, but only two pin holes?

you can buy the plugs at any french hypermarket
HTH
Dave
it would work with most french things, but it's not really just a french one, cos they often have a pin poking out, and a matching female bit in the plug
i'd call it a german one, but usually in practice, plugs fit both
edit: if you want me to post you one over, gis a pm
just a bare plug that you could wire to an extension lead would only be 1 euro or less
edit again: the earth is the bit going 90° to the two pins
i'd call it a german one, but usually in practice, plugs fit both
edit: if you want me to post you one over, gis a pm
just a bare plug that you could wire to an extension lead would only be 1 euro or less
edit again: the earth is the bit going 90° to the two pins
Edited by hugoagogo on Tuesday 14th October 16:22
I would be inclined to replace the whole socket, for the UK 3pin
type........Try Screwfix " MK industrial commando ( seriously ) socket
K9233 32A -240V-BLU " £8.49 inc VAT. That would allow you to use the
corresponding 3 pin plug.
Not too involved to change this over, if you're reasonably hands on.
type........Try Screwfix " MK industrial commando ( seriously ) socket
K9233 32A -240V-BLU " £8.49 inc VAT. That would allow you to use the
corresponding 3 pin plug.
Not too involved to change this over, if you're reasonably hands on.
It is not French. It is a Shucko, mainly used in Germany and some other European countries. The French version has an earth pin.
http://cpc.farnell.com/CN06990/electrical-lighting...
http://cpc.farnell.com/CN06990/electrical-lighting...
Edited by cjs on Tuesday 14th October 18:26
jag guru said:
I would be inclined to replace the whole socket, for the UK 3pin
type........Try Screwfix " MK industrial commando ( seriously ) socket
K9233 32A -240V-BLU " £8.49 inc VAT. That would allow you to use the
corresponding 3 pin plug.
Not too involved to change this over, if you're reasonably hands on.
A 32 amp socket would allow overload to the generator, its only 2.3kv which is about 10 amps.type........Try Screwfix " MK industrial commando ( seriously ) socket
K9233 32A -240V-BLU " £8.49 inc VAT. That would allow you to use the
corresponding 3 pin plug.
Not too involved to change this over, if you're reasonably hands on.
cjs said:
jag guru said:
I would be inclined to replace the whole socket, for the UK 3pin
type........Try Screwfix " MK industrial commando ( seriously ) socket
K9233 32A -240V-BLU " £8.49 inc VAT. That would allow you to use the
corresponding 3 pin plug.
Not too involved to change this over, if you're reasonably hands on.
A 32 amp socket would allow overload to the generator, its only 2.3kv which is about 10 amps.type........Try Screwfix " MK industrial commando ( seriously ) socket
K9233 32A -240V-BLU " £8.49 inc VAT. That would allow you to use the
corresponding 3 pin plug.
Not too involved to change this over, if you're reasonably hands on.
Ganglandboss said:
cjs said:
jag guru said:
I would be inclined to replace the whole socket, for the UK 3pin
type........Try Screwfix " MK industrial commando ( seriously ) socket
K9233 32A -240V-BLU " £8.49 inc VAT. That would allow you to use the
corresponding 3 pin plug.
Not too involved to change this over, if you're reasonably hands on.
A 32 amp socket would allow overload to the generator, its only 2.3kv which is about 10 amps.type........Try Screwfix " MK industrial commando ( seriously ) socket
K9233 32A -240V-BLU " £8.49 inc VAT. That would allow you to use the
corresponding 3 pin plug.
Not too involved to change this over, if you're reasonably hands on.
handling, not what the generator can supply.
So, OK use a 16A as Ganglandboss suggested. I listed this one as it was
the first IP44 240V socket I came to.
Yes, you are quite correct CJS, the max gen O/P is 10A ( I=P/V )
I humbly apologise for the ambiguous post !
Edited by jag guru on Wednesday 15th October 01:18
Ganglandboss said:
To add to what myself and jag guru have said, the rating of any accessory or cable must be equal to or greater than the rating of the protective device, not the other way round.
Ganglandboss is 100 % correct, as always.....Cheers Dave.